YASKAWA U1000 Series
Supplemental Technical Manual
Introduction
This supplemental technical manual describes the functions added with a U1000 software upgrade, and should
be read to ensure proper usage. Read this manual together with the U1000 Technical Manual (manual No. SIEP
C710636 02/ SIEP C710636 03/ SIEP C710636 04/ SIEP C710636 12) that can be found on the CD-ROM
delivered with the product or on our documentation website.
Always observe the safety messages and precautions to ensure correct application of the product.
・Parameters Modified by Standard Software Upgrade
Note: The software version is indicated on the nameplate affixed to the side of the product, and also can be
viewed by using monitor parameter U1-25.
・Enable the Internal EMC Filter
・EMC Guidelines Compliance
◆Parameters Modified by Standard Software Upgrade to PRG: 1018
This supplemental technical manual applies to U1000 software versions PRG: 1018 or later.
■Defaults by Drive Model Selection (o2-04)
Modified values are underlined.
200 V Class Drives Default Settings by Drive Model Selection (o2-04)
No. Name Unit Default Settings
– Model CIMR-U□ – 2□0104 2□0130 2□0154
HD ND HD ND HD ND
C6-01 Drive Duty Selection –
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. 70 72 73
E2-11 (E4-11) Motor Rated Output kW 22 30 30 37 37 45
L8-02 Overheat Alarm Level ℃ 136 136 136 136 134 134
No. Name Unit Default Settings
– Model CIMR-U□ – 2□0192 2□0248
HD ND HD ND
C6-01 Drive Duty Selection –
0 1 0 1
o2-04 Drive Model Selection Hex. 74 75
E2-11 (E4-11) Motor Rated Output kW 45 55 55 75
L8-02 Overheat Alarm Level ℃ 134 134 138 138
400 V Class Drives Default Settings by Drive Model Selection (o2-04)
No. Name Unit Default Settings
– Model CIMR-U□ – 4□0096 4□0124 4□0156
HD ND HD ND HD ND
C6-01 Drive Duty Selection –
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. A2 A3 A4
E2-11 (E4-11) Motor Rated Output kW 37 45 45 55 55 75
L8-02 Overheat Alarm Level ℃ 136 136 136 136 134 134
No. Name Unit Default Settings
– Model CIMR-U□ – 4□0180 4□0216 4□0240
HD ND HD ND HD ND
C6-01 Drive Duty Selection –
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. A5 A6 A7
E2-11 (E4-11) Motor Rated Output kW 75 90 90 110 110 132
L8-02 Overheat Alarm Level ℃ 134 134 138 138 138 138
No. Name Unit Default Settings
– Model CIMR-U□ – 4□0720 4□0900 4□0930
HD ND HD ND HD ND
C6-01 Drive Duty Selection –
0 1 0 1 0 1
o2-04 Drive Model Selection Hex. AE AF B0
E2-11 (E4-11) Motor Rated Output kW 300 375 375 450 450 500
L8-02 Overheat Alarm Level ℃ 140 140 140 140 140 140