o2-06: Operation Selection when HOA Keypad is Disconnected
Determines whether the drive will stop when the HOA keypad is removed in HAND mode or when b1-02 or b1-16 is set to
0. When the operator is reconnected, the display will indicate that it was disconnected.
No. Name Setting Range Default
o2-06 Operation Selection when HOA Keypad is Disconnected 0, 1 1
Setting 0: Continue Operation
The operation continues.
Setting 1: Trigger a Fault
The operation stops and triggers an oPr fault. The motor coasts to stop.
n
o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the HOA
keypad.
Note: This parameter is effective only when the Run command is set to be given from the HOA keypad (b1-02, b1-16 = 0).
No. Name Setting Range Default
o2-07 Motor Direction at Power Up when Using Operator 0, 1 0
Setting 0: Forward
Setting 1: Reverse
n
o2-19: Selection of Parameter Write during Uv
Selects whether parameter settings can be changed during a DC bus undervoltage condition. Used with 24 V Power Supply
option (PS-A10LB, PS-A10HB).
No. Name Setting Range Default
o2-19 Selection of Parameter Write during Uv 0, 1 0
Setting 0: Disabled
Setting 1: Enabled
u
o3: Copy Function
These parameters control the Copy function of the HOA keypad. The Copy function stores parameter settings into the memory
of the HOA keypad to facilitate the transfer of those settings to other drives that are the same model, capacity, and same control
mode setting.
n
o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No. Name Setting Range Default
o3-01 Copy Function Selection 0 to 3 0
Setting 0: Copy Select (No Function)
Setting 1: INV --> OP READ
Copies all parameters from the drive to the HOA keypad.
Note: The copy protection for the HOA keypad is enabled by default. Set o3-01 to 1 to unlock copy protection.
Setting 2: OP --> INV WRITE
Copies all parameters from the HOA keypad to the drive.
Setting 3: OP<-->INV VERIFY
Compares the parameters in the drive with the parameter settings saved on the HOA keypad for matches.
1.10 o: Operator-Related Settings
132
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage

Related product manuals