EasyManuals Logo

YASKAWA Z1000 CIMR-ZU*A Series User Manual

YASKAWA Z1000 CIMR-ZU*A Series
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #197 background imageLoading...
Page #197 background image
u
d7: Offset Frequency
No.
(Addr.
Hex)
Name LCD Display Description Setting Page
d7-01
(2B2)
Offset Frequency 1 Offset Freq 1
Added to the frequency reference when the digital input
“Frequency offset 1” (H1-oo = 44) is switched on.
Default: 0.0%
Min.: -100.0
Max.: 100.0
61
d7-02
(2B3)
Offset Frequency 2 Offset Freq 2
Added to the frequency reference when the digital input
“Frequency offset 2” (H1-oo = 45) is switched on.
Default: 0.0%
Min.: -100.0
Max.: 100.0
61
d7-03
(2B4)
Offset Frequency 3 Offset Freq 3
Added to the frequency reference when the digital input
“Frequency offset 3” (H1-oo = 46) is switched on.
Default: 0.0%
Min.: -100.0
Max.: 100.0
61
A.6 d: References
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
197
A
Parameter List

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage