B.11 BACnet Protocol Implementation Conformance Statement
Date: 1/4/2011 Vendor Name: Yaskawa America, Inc.
Product Name: AC Motor Controller Product
Model Number: CIMR-ZUA-□□□□
Application Software Version: 1.3 / Firmware Revision: VSE90101X / BACnet Protocol Revision: 4
Product Description:
The Yaskawa Z1000 Drive and Bypass products are high performance products specifically designed for commercial building
automation applications. The Yaskawa BACnet feature connects the Z1000 Drive and Bypass products to a standard BACnet
MS/TP network. These products may be fully controlled and monitored over BACnet. All drive parameters are available for
reading and writing
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing-ReadProperty-B (DS-RP-B)
Data Sharing-WriteProperty-B (DS-WP-B
Data Sharing - ReadProperty Multiple - B (DS-RPM-B)
Data Sharing - WriteProperty Multiple - B (DS-WPM-B)
Device Management-Dynamic Device Binding-B (DM-DDB-B)
Device Management-Dynamic Object Binding-B (DM-DOB-B)
Device Management-DeviceCommunicationControl-B (DM-DCC-B)
Device Management-ReinitializeDevice-B (DM-RD-B)
Device Management-TimeSyncronization-B (DM-TS-B)
Segmentation Capability:
Segmented requests supported / Window Size
Segmented responses supported / Window Size
Standard Object Types Supported:
Device Object
Analog Input Object
Analog Output Object
Analog Value Object
Binary Input Object
Binary Output Object
Binary Value Object
Data Link Layer Options:
BACnet IP, (Annex J)
BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
MS/TP master (Clause 9), baud rate(s): 1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200
MS/TP slave (Clause 9), baud rate(s):
B.11 BACnet Protocol Implementation Conformance Statement
264
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage