No.
(Addr.
Hex)
Name LCD Display Description Values Page
E2-04
(311)
Number of Motor Poles Number of Poles
Sets the number of motor poles. Automatically set during
Auto-Tuning.
Default: 4
Min.: 2
Max.: 48
67
E2-05
(312)
Motor Line-to-Line
Resistance
Term Resistance
Sets the phase-to-phase motor resistance. Automatically set
during Auto-Tuning.
Default:
<1>
Min.: 0.000 Ω
Max.: 65.000 Ω
67
E2-10
(317)
Motor Iron Loss for
Torque Compensation
Motor Iron Loss
Sets the motor iron loss.
Default:
<1>
Min.: 0 W
Max.: 65535 W
67
E2-11
(318)
Motor Rated Power Mtr Rated Power
Sets the motor rated power in kilowatts (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Default:
<1>
Min.: 0.00 kW
Max.: 650.00 kW
67
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
u
E5: PM Motor Settings
No.
(Addr.
Hex)
Name LCD Display Description Values Page
E5-02
(32A)
Motor Rated Power PM Mtr Capacity
OLV/PMOLV/PM
Sets the rated capacity of the motor.
Default:
<1>
Min.: 0.10 kW
Max.: 370.00 kW
68
E5-03
(32B)
Motor Rated Current PM Mtr Rated FLA
OLV/PMOLV/PM
Sets the motor rated current.
Default:
<1>
Min: 10% of
drive rated
current
Max: 200% of
drive rated
current
<2>
68
E5-04
(32C)
Number of Motor Poles PM Motor Poles
OLV/PMOLV/PM
Sets the number of motor poles.
Default:
<1>
Min.: 2
Max.: 48
68
E5-05
(32D)
Motor Stator Resistance PM Mtr Arm Ohms
OLV/PMOLV/PM
Set the resistance for each motor phase.
Default:
<1>
Min.: 0.000 Ω
Max.: 65.000 Ω
68
E5-06
(32E)
Motor d-Axis
Inductance
PM Mtr d Induct
OLV/PMOLV/PM
Sets the d-Axis inductance for the PM motor.
Default:
<1>
Min.: 0.00 mH
Max.: 300.00 mH
68
E5-07
(32F)
Motor q-Axis
Inductance
PM Mtr q Induct
OLV/PMOLV/PM
Sets the q-Axis inductance for the PM motor.
Default:
<1>
Min.: 0.00 mH
Max.: 600.00 mH
68
E5-09
(331)
Motor Induction Voltage
Constant 1
PM Mtr Ind V 1
OLV/PMOLV/PM
Sets the induced peak voltage per phase in units of
0.1 mV/(rad/s) [electrical angle]. Set this parameter when using
an IPM motor with variable torque.
Set E5-24 to 0 when setting this parameter.
Default:
<1>
Min.: 0.0 mV/
(rad/s)
Max.: 2000.0
mV/
(rad/s)
69
E5-24
(353)
Motor Induction Voltage
Constant 2
PM Mtr Ind V 2
OLV/PMOLV/PM
Sets the induced phase-to-phase rms voltage in units of
0.1 mV/(r/min) [mechanical angle].
Default:
<1>
Min.: 0.0 mV/
(r/min)
Max.: 6500.0
mV/
(r/min)
69
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units: 5A0007 to 5A0017: 0.01 A units; 5A0022 to 5A0242: 0.1 A units.
A.7 E: Motor Parameters
200
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage