PI feedback value
PI
Feedback
Detection
Loss Level
(b5-13)
PI Feedback
Loss Detection Time
(b5-14)
No FbL
detection
FbL detection
Time
PI Feedback
Loss Detection Time
(b5-14)
Figure 1.17 PI Feedback Loss Detection
n
b5-12: PI Feedback Loss Detection Selection
Enables or disables the feedback loss detection and sets the operation when a feedback loss is detected.
No. Parameter Name Setting Range Default
b5-12 PI Feedback Loss Detection Selection 0 to 5 0
Setting 0: Digital Output Only (Remains active when PI is disabled by digital input)
A digital output set for “PI feedback low” (H2-oo = 3E) will be triggered if the PI feedback value is below the detection
level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PI feedback high” (H2-oo = 3F) will be triggered
if the PI feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a fault nor an
alarm is displayed on the HOA keypad and the drive will continue operation. The output resets when the feedback value leaves
the loss detection range. Detection remains active when PI is disabled by digital input (H1-oo = 19).
Setting 1: Feedback Loss Alarm (Remains active when PI is disabled by digital input)
If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm
will be displayed and a digital output set for “PI feedback low” (H2-oo = 3E) will be triggered. If the PI feedback value
exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a
digital output set for “PI feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output (H1-oo = 10).
The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection range.
Detection remains active when PI is disabled by digital input (H1-oo = 19).
Setting 2: Feedback Loss Fault (Remains active when PI is disabled by digital input)
If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FbL - Feedback Low” fault
will be displayed. If the PI feedback value exceeds the level set to b5-36 for longer than the time set to b5-37, a “FbH - Feedback
High” fault will be displayed. Both events trigger a fault output (H1-oo = E) and cause the drive to stop the motor. Detection
remains active when PI is disabled by digital input (H1-oo = 19).
Setting 3: Digital Output Only
A digital output set for “PI feedback low” (H2-oo = 3E) will be triggered if the PI feedback value is below the detection
level set to b5-13 for the time set to b5-14 or longer. A digital output set for “PI feedback high” (H2-oo = 3F) will be triggered
if the PI feedback value is beyond the detection level set to b5-36 for longer than the time set to b5-37. Neither a fault nor an
alarm is displayed on the HOA keypad and the drive will continue operation. The output resets when the feedback value leaves
the loss detection range. Detection is disabled when PI is disabled by digital input (H1-oo = 19).
Setting 4: Feedback Loss Alarm
If the PI feedback value falls below the level set to b5-13 for longer than the time set to b5-14, a “FBL - Feedback Low” alarm
will be displayed and a digital output set for “PI feedback low” (H2-oo = 3E) will be triggered. If the PI feedback value
exceeds the level set to b5-36 for longer than the time set to b5-37, a “FBH - Feedback High” alarm will be displayed and a
digital output set for “PI feedback high” (H2-oo = 3F) will be triggered. Both events trigger an alarm output (H1-oo = 10).
The drive will continue operation. The alarm and outputs reset when the feedback value leaves the loss detection range.
Detection is disabled when PI is disabled by digital input (H1-oo = 19).
1.2 b: Application
42
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage

Related product manuals