Setting Specification Characteristic Application
8 50 Hz, Mid starting torque
High starting torque
Select high starting torque when:
Wiring between the drive and motor exceeds 150 m.
A large amount of starting torque is required.
An AC reactor is installed.
9 50 Hz, High starting torque
A 60 Hz, Mid starting torque
B 60 Hz, High starting torque
C 90 Hz (with 60 Hz base)
Constant output
Output voltage is constant when operating at greater than
60 Hz.
D 120 Hz (with 60 Hz base)
E 180 Hz (with 60 Hz base)
F
<1>
60 Hz Variable torque
Used for variable torque applications. The default setting is
the same as V/f pattern Setting 7.
<1> Setting F enables a custom V/f pattern by changing parameters E1-04 to E1-13. When the drive is shipped, the default values for parameters E1-04
to E1-13 are equal to predefined V/f pattern 7.
The following tables show details on predefined V/f patterns.
Predefined V/f Patterns for Models 5A0003 to 5A0009
Table 1.16 Constant Torque Characteristics, Settings 0 to 3
Setting = 0 50 Hz Setting = 1 60 Hz Setting = 2 60 Hz Setting = 3 72 Hz
0
25.9
575
1.3 2.5 50
43.1
Voltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3 60
Voltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3 6050
Voltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3 7260
Voltage (V)
Frequency (Hz)
Table 1.17 Derated Torque Characteristics, Settings 4 to 7
Setting = 4 50 Hz Setting = 5 50 Hz Setting = 6 60 Hz Setting = 7 60 Hz
0
23.0
575
1.3 25 50
100.6
Voltage (V)
Frequency (Hz)
0
25.9
575
1.3 25 50
143.8
Voltage (V)
Frequency (Hz)
0
23.0
575
1.5 30 60
100.6
Voltage (V)
Frequency (Hz)
0
25.9
575
1.5 30 60
143.8
Voltage (V)
Frequency (Hz)
Table 1.18 High Starting Torque, Settings 8 to B
Setting = 8 50 Hz Setting = 9 50 Hz Setting = A 60 Hz Setting = B 60 Hz
0
31.6
575
1.3 2.5 50
54.6
Voltage (V)
Frequency (Hz)
0
37.4
575
1.3 2.5 50
69.0
Voltage (V)
Frequency (Hz)
0
31.6
575
1.5 3 60
54.6
Voltage (V)
Frequency (Hz)
0
43.1
575
1.5 3 60
69.0
Voltage (V)
Frequency (Hz)
Table 1.19 Rated Output Operation, Settings C to F
Setting = C 90 Hz Setting = D 120 Hz Setting = E 180 Hz Setting = F 60 Hz
0
25.9
43.1
575
1.5 3 9060
Voltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3 12060
Voltage (V)
Frequency (Hz)
0
25.9
43.1
575
1.5 3 18060
Voltage (V)
Frequency (Hz)
0
25.9
575
1.5 30 60
143.8
Voltage (V)
Frequency (Hz)
1.5 E: Motor Parameters
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
63
1
Parameter Details

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage