Status Description
Open Output frequency or motor speed exceeded L4-01 + L4-02.
Closed Output frequency or motor speed is below L4-01 or has not exceeded L4-01 + L4-02.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
L4-02
Frequency
detection 1
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
Figure 1.43 Frequency Detection 1 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 110 for more details.
Setting 5: Frequency Detection 2
The output closes when the output frequency or motor speed is above the detection level set in L4-01. The terminal remains
closed until the output frequency or motor speed fall below L4-01 minus the setting of L4-02.
Status Description
Open Output frequency or motor speed is below L4-01 minus L4-02 or has not exceeded L4-01.
Closed Output frequency or motor speed exceeded L4-01.
Note: Frequency detection works in forward and reverse. The value of L4-01 is used as the detection level for both directions.
L4-02
Frequency
Detection 2
ON
OFF
L4-02
L4-01
L4-01
Output Frequency
Figure 1.44 Frequency Detection 2 Time Chart
Refer to L4-01, L4-02: Speed Agreement Detection Level and Detection Width on page 110 for more details.
Setting 6: Drive Ready
The output closes when the drive is ready to operate the motor. The terminal will not close under the conditions listed below,
and any Run commands will be disregarded.
When the power is shut off
During a fault
When the internal power supply of the drive has malfunctioned
When a parameter setting error makes it impossible to run
Although stopped, an overvoltage or undervoltage situation occurs
While editing a parameter in the Programming Mode (when b1-08 = 0)
1.7 H: Terminal Functions
YASKAWA SIEP YAIZ1U 03B YASKAWA AC Drive – Z1000 Programming Manual
85
1
Parameter Details

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA Z1000 CIMR-ZU*A Series and is the answer not in the manual?

YASKAWA Z1000 CIMR-ZU*A Series Specifications

General IconGeneral
SeriesZ1000 CIMR-ZU*A Series
CategoryController
Voltage Classes200V, 400V
EnclosureNEMA 1, NEMA 12
Frequency Range0.01 to 400 Hz
Cooling MethodFan Cooled
Operating Temperature-10°C to 50°C
ApplicationHVAC
Control MethodV/f Control
Input Voltage200-240V, 380-480V
Frequency Range (Input)50/60 Hz
Power Rating0.4kW to 630kW
Protection FeaturesOvercurrent, Overvoltage, Undervoltage
Communication OptionsModbus
Storage Temperature-20°C to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Output Voltage0-100% of input voltage

Related product manuals