EasyManuals Logo

Zener MSC-3 User Manual

Zener MSC-3
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #102 background imageLoading...
Page #102 background image
IM00120
88
IM00120
MSC-3 Start Up
F09 COMMS PRESET
F09 COMMS PRESET
60.0%
Range: -100.0...100.0 % of C03 MAX Hz
• Press to edit the value.
• Press / to make changes to the value.
• Press to accept the new value OR
• Press ESC to abandon the value change.
The F09 COMMS PRESET parameter is the power-on value for the > COMMS REF reference. The
> COMMS REF is the reference by the operating communication network protocol.In the event that
communications is lost, the COMMS REF reference will automatically revert to the F09 COMMS
PRESET parameter value. See G168 Comms Lost Time on page 112 for further details. Setting G168
Comms Lost Time to zero disables the detection of communications loss.
F10 PRESETS
There are 8 preset references for the MSC-3. Most are used in conjunction with the Reference Selector.
Each preset is expressed as a percentage of C03 MAX Hz.
F100 PRESET1 to F107 PRESET8
F100 PRESET 1
10.0%
F104 PRESET 5
50.0%
F101 PRESET 2
20.0%
F105 PRESET 6
60.0%
F102 PRESET 3
30.0%
F106 PRESET 7
70.0%
F103 PRESET 4
40.0%
F107 PRESET 8
80.0%
Range: -100.0...100.0 % of C03 MAX Hz
• Press to edit the value.
• Press / to make changes to the value.
• Press to accept the new value OR
• Press ESC to abandon the value change.