MSC-3 Instruction Manual
• Press ESC to abandon the value change.
Regardless of how the analogue input is congured the maximum reference for input spanning is
determined by this parameter. The G024 Ref @MAX in parameter corresponds to the G022 MAX input
to dene the input spanning conguration. See the Analogue Inputs and Spanning feature for details.
G025 Hi Compare Level
G025 Hi Compare
Level: 8.0V
Range: 0.0...10.0 V or 0.0 to 20 mA
• Press to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press to accept the new value OR
• Press ESC to abandon the value change.
If the G020 Input Type is congured for > Volts then G025 Hi Compare Level will be displayed with
units of volts (V) otherwise G025 Hi Compare Level will be displayed with units of milliamps (mA). In
either case the high level compare threshold is determined by this parameter. When the input rises
above this level, the compare output will be true (high). See the Analogue Inputs and Spanning feature
for details.
G026 LoCMP Level
G026 Lo Compare
Level: 2.0V
Range: 0.0...10.0 V or 0.0 to 20 mA
• Press to edit the value.
• Press ▲/ ▼ to make changes to the value.
• Press to accept the new value OR
• Press ESC to abandon the value change.