MSC-3 Instruction Manual
Extended Feature Option Cards
The MSC-3 may be tted with 1 or 2 extended features cards. Each card provides additional analogue
and digital inputs and outputs. The cards may be tted in either the left or right option card sockets.
The MSC-3 will detect the presence of the option cards and commence exchanging I/O status data.
Additional options will appear in the selection lists and accesses to additional menus are available for
extended feature set up.
Extended Feature Analogue Output
Each extended feature card for the MSC-3 makes available a single analogue output for those
applications that require feedback of an internal signal. The analogue output is designed with the
following features:
• Congurable voltage (V) or current (mA) input conguration.
• Signal source selection
• Easy to congure spanning and translation.
The diagram below illustrates the design:
G112 Signal MIN
G111 AN OUT sel
Motor Current
% Load
Output Power
I
2
t
Speed
Analogue
Ouput
Signal
Selection
Analogue
Ouput
Circuitry
Output (V or mA)
Signal
G115 MAX Output
G114 MIN Output
G113 Signal MAX
G110 AN OUT mode
Key (left-hand option connector) conguration parameters are:
• G110 AN OUT mode (mA or V selection)
• G111 AN OUT sel (signal source selection)
• G112 Signal MIN and G113 Signal MAX
• G114 MIN Output and G115 MAX Output
Refer to G150…G155 for Extended Features AN OUT in the right-hand option connector