EasyManua.ls Logo

ABB ACS180 - Page 42

ABB ACS180
392 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42 Control macros
Notes:
1)
See parameters 40.19 Set 1 internal setpoint sel1and 40.20 Set 1 internal setpoint
sel2 source table.
2)
Select the correct control mode from the Motor data view or with parameter 99.04
Motor control mode.
3)
PID: 010 V -> 0100% PID setpoint.
4)
The signal source is powered externally. See the manufacturer’s instructions. To
use sensors supplied by the drive aux. voltage output, see connection examples of
two-wire and three-wire sensors in the hardware manual of the drive.
5)
Ground the outer shield of the cable 360 degrees under the grounding clamp on
the grounding shelf for the control cables.
6)
Select the unit for analog input AI1 in the parameter 12.15 and for AI2 in the
parameter 12.25.
Input signals
PID set point (AI1)
Process feedback (AI2)
Start/stop selection (DI1)
Internal setpoint selection 1 (DI2)
Internal setpoint selection 2 (DI3)
Constant speed selection 1 (DI4)
Output signals
Digital output: Running
Relay output: Fault(-1)
Analog output AO: Output frequency
Source defined
by par. 40.19
DI2
Source defined
by par. 40.20
DI3
Internal setpoint active
00
Setpoint source: AI1 (par.40.16)
10
Internal setpoint 1 (par. 40.21)
01
Internal setpoint 2 (par. 40.22)
11
Internal setpoint 3 (par.40.23)
DI4 Operation/Parameter
Scalar control (default) Vector control
0 Set frequency through AI1 Set speed through AI1
1 28.26 Constant frequency 1 22.26 Constant speed 1
ACS180 FW.book Page 42 Tuesday, March 9, 2021 2:25 PM

Table of Contents

Other manuals for ABB ACS180

Related product manuals