ACS2000 User manual 2UEA001270 Rev. F 5-7 (14)
Chapter 5 - Mechanical installation
7 Reattach the rear and the cover of the external fan.
Removal procedure is the reverse of the installation procedure.
5.4.5 Redundant fan installation - Frame 1 (option)
The redundant fan unit and the required fastening screws are supplied
separately.
Figure 5-5 - Frame 1 Redundant fan unit
Dimensions (L x W x H) 1150 x 840 x 355 mm [45 x 33 x 14 in]
Weight Approximately 114 kg [250 lbs]
Tools Torx screwdriver for removing/installing the side panels of the fan or
10 mm hex wrench to install the hexagon fastening hardware.
WARNING
Wiring connections will need to be made. Make sure no power is
connected to the drive before proceeding with redundant fan installation.
5.4.5.1 Redundant fan installation procedure - Frame 1
Consider the size and weight of the components when planning to lift them
onto the top of drive.
The fan components can be lifted by means of a forklift or a crane.
1 Remove the cover and the fan from the redundant fan assembly.