EasyManua.ls Logo

ABB ACS2000 - Procedure for Disconnecting the Drive from the Main Power Supply

ABB ACS2000
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ACS2000 User manual 2UEA001270 Rev. F 8-13 (18)
Chapter 8 - Local operation
8.7.1 Procedure for disconnecting the drive from the main power supply
1 Stop the motor as
described in the
previous section.
When the motor has reached zero speed, the display shows
ReadyRun.
2 Press the SUPPLY
OFF pushbutton to
disconnect the drive
from the main power
supply.
The following takes place:
The MV switchgear opens.
The DC link discharges.
While the DC link discharges, the display shows
OffSeqOn.
The SUPPLY OFF pushbutton flashes and changes to a
steady light when the DC link is discharged completely.
When the DC link is discharged, the display shows
ReadyOn.
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm
StateINU
OffSeqOn
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm
StateINU
ReadyOn
MOTOR SP 0.00 rpm
POWER
0.0 kW

Table of Contents

Related product manuals