6-6 (16) 2UEA001270 Rev. F ACS2000 User manual
Chapter 6 - Electrical installation
6.4.2 Cable entry for ground cable, line supply and motor cables
Cable entry for ground cable, line supply and motor cables (1) is separate
from the entry for auxiliary power and control cables (2).
Figure 6-3 Cable entry
The entry plate for ground, line supply and motor cables (1 in Figure 6-3)
is a 6.4 mm [0.25 in] thick aluminum plate. The entry holes need to be
punched on-site to properly accommodate customer cables.
This aluminum plate is either attached to the top or the bottom access
hole - whichever is receiving the cables.
The unused entry access hole is covered by a steel plate.
6.4.3 Cable entry for auxiliary power and control cables
The cable entry access holes for the auxiliary power and control cables
(2 in Figure 6-3) are covered by an aluminum plate.
This aluminum plate needs to be punched on-site to properly
accommodate the customer incoming cables.
This aluminum plate is either attached to the top or the bottom access
hole - whichever is receiving the cables.
The unused entry access hole is covered by a steel plate.
Legend
1 Cable entry - ground,
line and motor cables
2 Cable entry - auxiliary
power and control
cables
1
2
Front of drive