3-20 (26) 2UEA001270 Rev. F ACS2000 User manual
Chapter 3 - Control system
3.3.3.1 IOEC4 (A1621) digital outputs
Table 3-8 Optional digital output signal allocation
Terminal Channel Default setting Par. Group
X21-1
DO01
Freely programmable
X21-2
X21-3
X22-1
DO02
Freely programmable
X22-2
X22-3
X23-1
DO03
Freely programmable
(for motor space heater then
motor heater OFF command)
X23-2
X23-3
X24-1
DO04
Freely programmable
(for motor cooling fan then
motor cooling fan ON command)
X24-2
X24-3
X25-1
DO05
Freely programmable
X25-2
X25-3
X26-1
DO06
Freely programmable
X26-2
X26-3
DC voltage Current
Switching Continuous
24 VDC 8A 6A
48 VDC 1A 6A
120 VDC 0.4A 6A
AC voltage Current
Switching Continuous
24 VAC 8A 6A
48 VAC 8A 6A
120 VAC 8A 6A
230 VAC 8A 6A
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO