2-20 (28) 2UEA001270 Rev. F ACS2000 User manual
Chapter 2 - Power electronics and cabinet features
Figure 2-17 Auxiliary power supply connections
Table 2-1 Current consumption during precharge and auxiliary power
supply requirement
2.4.1.1 Single-phase control power (option)
The control system can be supplied via a single-phase power supply. See
Table 2-2 for the phase voltage and normal running current of the drive.
This option has the advantage that the main control hardware will remain
energized and the full ride-through capabilities of the drive can be used. In
the event of a 480 V auxiliary power outage, communication to a higher-
level control system will not be lost. This control supply is wired to terminal
block X02. See Figure 2-17.
Auxiliary power
supply voltage
Current
consumption
during precharge
(A)
Precharge
time
(s)
System
current
(A)
Power
requirement
(kVA)
Frame 1
480 V 21 8 8 6
400 V (option) 25 11 9 6
600 V (option) 17 8 6 6
Frame 2
480 V 28 18 14 11
400 V (option) 33 24 16 11
600 V (option) 22 18 11 11
Frame 3
480 V 33 27 21 17
400 V (option) 40 39 25 17
600 V (option) 27 27 17 17
102
(
L-out
)
103
(
N-out
)
100
(
L1
)
101
(
L2
)
102
(
L3
)
100
(
L
)
101
(
N
)
100
(
L
)
101
(
N
)
PE
PE
PE
PE
PE
100
(
L-in
)
101
(
N-in
)
3
Legend
1 Terminal Block X01: Three-phase auxiliary power supply
2 Terminal Block X02: Single-phase control power supply (option)
3 Terminal Block X19: Motor space heater protection (option)
4 Terminal Block X20: Converter space heater power supply (option)
12 4