ACS2000 User manual 2UEA001270 Rev. F 8-9 (18)
Chapter 8 - Local operation
8.5.3 Starting the drive system locally
Note: The motor is controlled by the INU of the drive. For this reason, the
CDP control panel must be connected to the INU to be able to start the
drive system locally. The CDP control panel is only connected to the AFE
if it is required to view status and fault messages of the AFE.
When the drive system is running, the CDP control panel can be
connected intermittently without interrupting the operation of the drive.
However, to stop the drive system, the CDP control panel must be
connected to the INU. Switching the CDP control panel from the INU to the
AFE and back is done with the drive selection mode.
See section 9.3.5 Drive selection mode for further information.
8.5.3.1 Procedure for starting locally
1 Check that the CDP
control panel is
connected to the INU.
2 Set the CDP control
panel to LOCAL mode
3 Check that no alarm or
fault messages are
displayed on the CDP
control panel.
When a fault message is displayed on the CDP control panel, reset
the fault.
If a fault cannot be reset, it must be rectified by the responsible
personnel.
See Chapter 10 - Troubleshooting and maintenance, 10.3
Troubleshooting for further information.
When no alarms and faults are present and the drive is ready, the
CDP control panel displays ReadyOn.
1 L ->
0.0 rpm
StateINU
ReadyOn
MOTOR SP 0.00 rpm
POWER
0.0 kW