8-10 (18) 2UEA001270 Rev. F ACS2000 User manual
Chapter 8 - Local operation
4 Press the SUPPLY
ON pushbutton on the
control compartment
door to charge the DC
link. The pushbutton
flashes during
charging.
The status line of the CDP control panel alternates between
Charging and AuxiliaryOn.
After charging is finished:
• The MV switchgear closes automatically.
• The SUPPLY ON pushbutton lights up steady.
• The AFE starts to modulate.
If the CDP control panel was switched to the AFE, you will see
the message Modulating, and then after a short instant, the
message ReadyRef in the status line of the display.
When the AFE is in ReadyRef state, the state of the INU changes to
ReadyRun and the motor can be started.
See Flow diagram in section 8.4.2 Start sequence of the drive.
5 Enter the setpoint. See section 9.4.3 Entering a setpoint for procedure.
AuxiliaryOn
Charging
1 L ->
0.0 rpm
StateINU
Charging
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
0.0 rpm 0
StateINU
ReadyRun
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
[600.0 rpm] 0
StateINU
ReadyRun
MOTOR SP 0.00 rpm
POWER
0.0 kW