5-2 (14) 2UEA001270 Rev. F ACS2000 User manual
Chapter 5 - Mechanical installation
See Appendix C - Technical data/environment/operation, located on
the CD, for detailed information.
5.3.2 Foundation requirements
The floor must be a non-flammable, smooth, level, moisture-free surface
able to support the weight of the drive.
Table 5-1 Cabinet weight
The floor must be flat overall within a recommended maximum slope of
≤ 5 mm [0.2 in]/5 m [16.4 ft].
See Appendix D - Mechanical drawings, located on the CD, for details on
the specific weight of the cabinet.
See Appendix P - Integral Input Contactor Disconnect, located on the CD,
for additional weight if this option is included on the drive.
5.3.3 Recommendations for cable ducts and fire protection
Cable ducts should be of non-flammable material with non-abrasive
surface.
All cable entries and exits should be protected to prevent dust, humidity
and animals from entering into the drive.
Suitable fire protection measures should be applied to prevent fire from
spreading into the drive.
5.4 Drive installation
5.4.1 General notes on installation
When installing the drive, ensure that no dirt enters. Always close the
doors when work is discontinued and completely cover openings. Metallic
dust, in particular, may cause malfunction when the drive is powered up
and may cause damage.
The cabinet roof is not designed as a mounting base for foreign devices,
cable ducts, etc. Therefore, do not install any foreign device on the top of
the drive.
Frame
Standard
weight
kg [lbs]
With integral
disconnect weight
kg [lbs]
1 2495 [5500] 3130 [6900]
2 2950 [6500] 3585 [7900]
3 3855 [8500] 4490 [9900]