Actual signals and parameters
96
30.15 UNDERLOAD CURVE Selects the load curve for the underload function.
See 30.13 UNDERLOAD FUNC.
1…5 Number of the load curve 1 = 1
30.16 MOTOR PHASE LOSS Activates the motor phase loss supervision function.
See section Motor Phase Loss on page 39.
NO Inactive 0
FAULT Active. The drive trips on a fault. 65535
30.17 GROUND FAULT Selects how the drive reacts when an ground fault is detected in the
motor or the motor cable.
See section Ground Fault Protection on page 40.
WARNING The drive generates a warning. 0
FAULT The drive trips on a fault. 65535
30.18 COMM FLT FUNC Action the drive will take when a COMM MOD LOSS is detected.
NO ERR CHK Fieldbus communication loss is not checked. 1
RAMP STOP The drive will ramp to a stop and show a warning. 2
COAST STOP The drive will fault, remove the run command and coast to a stop. 3
30.19 COMM TIMEOUT The delay time before a COMM MOD LOSS is declared.
0…60000 ms Setting range. 1 = 1 ms
32 SUPERVISION
Supervision limits.
32.01 SPEED1 FUNCTION Activates/deactivates the speed supervision function and selects the
type of the supervision limit.
NO Supervision is not used. 1
LOW LIMIT Supervision wakes up if the value is below the limit. 2
HIGH LIMIT Supervision wakes up if the value is above the limit. 3