Actual signals and parameters
72
DI5 See selection DI2. 5
DI6 See selection DI2. 6
DI7 See selection DI2. 7
DI8 See selection DI2. 8
DI9 See selection DI2. 9
DI10 See selection DI2. 10
DI11 See selection DI2. 11
DI12 See selection DI2. 12
FIELDBUS See selection DI2. Instead of a digital input, the selection comes from
06.01 DATASET 1 WORD 1 bit 09. See chapter Fieldbus control.
13
PARAM 12.09 Source selected by 12.09 TAKE-UP/PAYOUT PTR 14
12.07 SPEED CHANGE Defines take-up/payout speed adder.
+/- 11.05 EXT1 REF MAX Setting range. 1 = 1 rpm
12.08 CNST SPD RUN SEL Selects if the drive is to start when the digital inputs used in 12.01
CONST SPEED SEL = 1 or if the run command is required.
MNSTRT REQ A separate run command is required to start the drive. 0
STRT W/CNST The drive starts when the constant speed digital input = 1. 1
12.09 TAKEUP/PAYOUT PTR Defines the source or constant for selection PARAM 12.09 of
12.06 TAKEUP/PAYOUT
-255.255.31…+255.255.31
/ C.-32768…C.32767
Parameter index or a constant value. See 10.05 EXT1 STRT PTR for
information on the difference.
-
13 ANALOG INPUTS
The analog input signal processing
13.01 MINIMUM AI1 Defines the minimum value for analog input AI1. When used as a
reference, the value corresponds to the reference minimum setting.
Example: If AI1 is selected as the source for external reference 1, this
value corresponds to the value of 11.04 EXT1 REF MINIMUM.
0 V Zero Volts.
Note: The program cannot detect a loss of analog input signal.
1
2 V Two Volts 2
TUNED VALUE The value measured by the tuning function. See selection TUNE. 3
TUNE The value measurement triggering. Procedure:
- Connect the minimum signal to input.
- Set the parameter to TUNE.
Note: The readable range in tuning is 0 V to 10 V.
4
No. Name/Value Description FbEq