Actual signals and parameters
128
TOFF 9
TON 8
TRIGG 6
WR-I 27
W-PB 28
XOR 4
84.06 INPUT1 Selects the source for input I1 of Block Parameter Set 1.
-255.255.31…+255.255.31
/ C.-32768…C.32767
Parameter index or a constant value:
- Parameter pointer: Inversion, group, index and bit fields. The bit
number is effective only for blocks handling boolean inputs.
- Constant value: Inversion and constant fields. Inversion field must
have value C to enable the constant setting.
Example: The state of digital input DI2 is connected to Input 1 as
follows:
- Set the source selection parameter (84.06) to +.01.17.01. (The
control program stores the state of digital input DI2 to bit 1 of actual
signal 01.17.)
- If you need an inverted value, switch the sign of the pointer value
(-01.17.01.).
-
84.07 INPUT2 See 84.06 INPUT1.
-255.255.31…+255.255.31
/ C.-32768…C.32767
See 84.06 INPUT1. -
84.08 INPUT3 See 84.06 INPUT1.
-255.255.31…+255.255.31
/ C.-32768…C.32767
See 84.06 INPUT1. -
84.09 OUTPUT Stores and displays the output of Block Parameter Set 1. -
… …
84.79 OUTPUT Stores the output of Block Parameter Set 15. -
85 USER CONSTANTS
Storage of the Adaptive Program constants and messages. For more
information, see Adaptive Program Application Guide (code: 3AFE
64527274 [English])
85.01 CONSTANT1 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
85.02 CONSTANT2 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
85.03 CONSTANT3 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
85.04 CONSTANT4 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
85.05 CONSTANT5 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
85.06 CONSTANT6 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
85.07 CONSTANT7 Sets a constant for the Adaptive Program.
-8388608 to 8388607 Integer value. 1 = 1
No. Name/Value Description FbEq