Start-up
7
How to perform the ID Run
For this application, the Standard ID Run must be performed.
Uncouple the motor from the spool if possible. If the motor cannot be uncoupled from
the spool, ensure the spool is at core.
Note: DIIL must be made and 16.01 RUN ENABLE must be set to “Yes” or the digital
input made in order to perform the ID Run.
ID Run Procedure
Note: If parameter values (Group 10 to 98) are changed before the ID Run, check
that the new settings meet the following conditions:
20.01 MINIMUM SPEED <
0 rpm
20.02 MAXIMUM SPEED > 80% of motor rated speed
20.03 MAXIMUM CURRENT >
100% · I
hd
20.04 MAXIMUM TORQUE > 50%
22.02 ACCEL TIME 1 <
1 s
70.06 CH2 M/F MODE - Set to “Not In Use”
Ensure that the panel is in the local control mode (L displayed on the status row).
Press the LOC/REM key to switch between modes.
Change the selection to STANDARD.
•Press ENTER to verify selection. The following message will be displayed:
To start the ID Run, press the key.
Warning when the ID Run is
started
Warning during the ID Run Warning after a successfully
completed ID Run
1 L -> 1242.0 rpm I
ACS 800 55 kW
**WARNING**
MOTOR STARTS
1 L -> 1242.0 rpm I
ACS 800 55 kW
**WARNING**
ID RUN
1 L -> 1242.0 rpm I
ACS 800 55 kW
**WARNING**
ID DONE
99 START-UP DATA
10 MOTOR ID RUN
[STANDARD]
1 L ->1242.0 rpm O
1 L ->1242.0 rpm O
ACS 800 55 kW
**WARNING**
ID RUN SEL