Actual signals and parameters
136
RAIO-DDCS Communication active. Module type: RAIO. Connection interface:
Optional I/O module adapter (AIMA) that communicates with the drive
through a fibre optic DDCS link.
Note: Set the module node number to 9. For directions, see User’s
Manual for RAIO Module (Code: 3AFE64484567 [English]).
5
98.13 AI/O EXT AI1 FUNC This parameter defines the configuration for external analog input AI1.
The selection must match the dip switch settings in the module.
UNIPOLAR A15 Integer default. 1
BIPOLAR A15 Integer. 2
98.14 AI/O EXT AI2 FUNC This parameter defines the configuration for external analog input AI2.
The selection must match the dip switch settings in the module.
UNIPOLAR AI6 Integer default. 1
BIPOLAR AI6 Integer. 2
99 START-UP DATA
Drive set-up.
99.01 LANGUAGE Selects the display language.
ENGLISH British English 0
ENGLISH (AM) American English. If selected, the unit of power used is Hp instead of
kW.
1
DEUTSCH German 2
ITALIANO Italian 3
ESPANOL Spanish 4
PORTUGUES Portuguese 5
NEDERLANDS Dutch 6
FRANCAIS French 7
DANSK Danish 8
SUOMI Finnish 9
SVENSKA Swedish 10
CESKY Czech 11
POLSKI / LOC1 Polish 12
PO RUS / LOC2 Russian 13
99.02 APPLICATION MACRO Selects the application macro. See chapter Application macros for
more information.
Note: Even you change the default parameter values of a macro, the
new settings becomes valid immediately and stay valid even if the
power of the drive is switched off and on. However, backup of the
default parameter settings (factory settings) of each standard macro is
still available. See 99.03 APPLIC RESTORE.
UNWIND – TEN Unwind section with tension/torque control. 1
UNWIND – DAN Unwind section with a dancer. 2
WINDER – TEN Winder section with tension/torque control. 3
WINDER – DAN Winder section with a dancer. 4
WINDER – LD Winder section that is machine master. 5
TORQ FOLLOW Torque follower macro. 6
No. Name/Value Description FbEq