Actual signals and parameters
137
USER 1 LOAD User 1 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the
application.
7
USER 1 SAVE Save User 1 macro. Stores the current parameter settings and the
motor model.
Note: There are parameters that are not included in the macros. See
99.03 APPLIC RESTORE.
8
USER 2 LOAD User 2 macro loaded into use. Before loading, check that the saved
parameter settings and the motor model are suitable for the
application.
9
USER 2 SAVE Save User 2 macro. Stores the current parameter settings and the
motor model.
Note: There are parameters that are not included in the macros. See
99.03 APPLIC RESTORE.
10
99.03 APPLIC RESTORE Restores the original settings of the active application macro (99.02
APPLICATION MACRO).
- If a standard macro is active, the parameter values are restored to
the default settings (factory settings). Exceptions: parameter settings
in group 99 START-UP DATA remain unchanged. The motor model
remains unchanged.
- If User Macro 1 or 2 is active, the parameter values are restored to
the last saved values. In addition, the last saved motor model are
restored. Exceptions: Settings of 16.05 USER MACRO IO CHG and
99.02 APPLICATION MACRO remain unchanged.
Note: The parameter settings and the motor model are restored
according to the same principles when a macro is changed to another.
NO No restoring. 0
YES Restoring. 65535
99.05 MOTOR NOM VOLTAGE Defines the nominal motor voltage. Must be equal to the value on the
motor rating plate.
½…2 x U
N
Voltage. Allowed range is 1/2…2 · U
N
of the drive. 1 = 1 V
99.06 MOTOR NOM CURRENT Defines the nominal motor current. Must be equal to the value on the
motor rating plate.
Note: Correct motor run requires that the magnetizing current of the
motor does not exceed 90 percent of the nominal current of the
inverter.
1/6…2 x I
2hd
Allowed range: 1/6…2 · I
2hd
of ACS800. 10 = 1 A
99.07 MOTOR NOM FREQ Defines the nominal motor frequency.
8…300 Hz Nominal frequency (50 or 60 Hz typically) 100 = 1 Hz
99.08 MOTOR NOM SPEED Defines the nominal motor speed. Must be equal to the value on the
motor rating plate. The motor synchronous speed or another
approximate value must not be given instead!
Note: If the value of 99.08 is changed, the speed limits in group 20
LIMITS change automatically as well.
1…18000 rpm Nominal motor speed. 1 = 1 rpm
99.09 MOTOR NOM POWER Defines the nominal motor power. Set exactly as on the motor rating
plate.
0…9000 kW
0…9000 Hp
Nominal motor power. 10 = 1 kW
10 = 1 Hp
No. Name/Value Description FbEq