Actual signals and parameters
100
50.08 ENC CABLE CHECK Selects the drive operation when encoder signal is missing.
Note: Monitoring is only for RTAC-03. For more information, see
RTAC-03 Pulse Encoder Interface Module User’s Manual
[3AFE68650500 (English)].
NO No action. 0
WARNING Drive generates warning ENC CABLE. 1
FAULT Drive trips on fault ENC CABLE. 2
51 FIELDBUS DATA
The parameters are visible and need to be adjusted only when a
fieldbus adapter module (optional) is installed and activated by 98.02
FIELDBUS MODULE. For details on the parameters, refer to the
manual of the fieldbus module.
These parameter settings will remain the same even if the macro is
changed.
52 STANDARD MODBUS
The setting for the standard modbus link.This group will be Visible only
when Standard Modbus is selected by 98.02 FIELDBUS MODULE
and ensure that RMBA module is inserted in Option Slot1.
52.01 STATION NUMBER Defines the address of the device. Two units with the same address
are not allowed on-line.
1…247 Address 1 = 1
52.02 BAUDRATE Defines the transfer rate of the link.
600 600 bit/s. 1
1200 1200 bit/s. 2
2400 2400 bit/s. 3
4800 4800 bit/s. 4
9600 9600 bit/s. 5
19200 19200 bits/s. 6
52.03 PARITY Defines the use of parity and stop bit(s). The same setting must be
used in all on-line stations.
NONE1STOPBIT No parity bit, one stop bit. 1
NONE2STOPBIT No parity bit, two stop bits. 2
ODD Odd parity indication bit, one stopbit. 3
EVEN Even parity indication bit, one stopbit. 4
60 APPLIC CONTROLS
Non-macro specific winder parameters.
60.01 INERTIA COMP ENBL Allows inertia compensation to be used and makes Group 64 visible.
NO Inertia compensation is not needed. 0
YES Inertia compensation is needed. 65535
60.02 GEAR RATIO Ratio between motor rpm and spindle rpm.
0.10…1000.00 (:1) Setting range. 100 = 1
60.03 WEB LOSS TRIP The percent (of maximum tension) deviation allowed before error
detection.
0.0…100.0% Setting range. 10 = 1%
No. Name/Value Description FbEq