Actual signals and parameters
125
0…20000 Setting range. 1 = 1
70.08 MASTER SIGNAL 2 Signal pointer for high speed dataset communications to followers as
Reference 1 (speed reference).
0…20000 Setting range. 1 = 1
70.09 MASTER SIGNAL 3 Signal pointer for high speed dataset communications to followers as
Reference 2 (torque reference).
0…20000 Setting range. 1 = 1
70.10 M/F COMM DELAY The delay time before a M/F COMM LOSS is declared.
0…8388607 ms Setting range. 1 = 1 ms
70.11 M/F COM LOSS CTRL Action the drive will take when a M/F COMM LOSS is detected.
NO ERR CHK CH2 communication loss is not checked. 1
RAMP STOP The drive will ramp to a stop and show a warning. 2
COAST STOP The drive will fault, remove the run command and coast to a stop. 3
70.12 CHANNEL 3 ADDR Node address for channel 3. No two nodes on-line may have the same
address. Typically the setting needs to be changed when the drive is
connected in a ring which consists of several drives and a PC with the
DriveWindow® program running.
1…254 Address. 1 = 1
70.13 NUM OF TQ FOLLWR This parameter defines the number of torque follower drives that are
being used. This will scale the torque reference to the total available
motor torque when using open or closed loop torque control. The
application assumes the motors to be identically rated.
0…4 Setting range. 1 = 1
83 ADAPT PROG CTRL
Control of the Adaptive Program execution. For more information, see
Adaptive Program Application Guide (code: 3AFE64527274
[English]).
83.01 ADAPT PROG CMD Selects the operation mode for the Adaptive Program.
STOP Stop. The program cannot be edited. 1
RUN Run. The program cannot be edited. 2
EDIT Stop to edit mode. Program can be edited. 3
83.02 EDIT COMMAND Selects the command for the block placed in the location defined by
83.03 EDIT BLOCK. The program must be in editing mode (see
83.01 ADAPT PROG CMD).
NO Home value. The value automatically restores to NO after an editing
command has been executed.
1
No. Name/Value Description FbEq