Actual signals and parameters
71
DI3 Digital input DI3 = 1 selects 12.02 CONST SPD 1. 2
DI3, DI4 Digital input DI3 = 1 selects 12.02 CONST SPD 1. Digital input DI4 = 1
selects 12.03 CONST SPD 2.
3
DI5 See selection DI3. 4
DI5, DI6 See selection DI3, DI4. 5
DI7 See selection DI3. 6
DI7, DI8 See selection DI3, DI4. 7
DI9 See selection DI3. 8
DI9, DI10 See selection DI3, DI4. 9
DI11 See selection DI3 10
DI11, DI12 See selection DI3, DI4. 11
FIELDBUS See selection DI3, DI4. Instead of digital inputs, the selection comes
from 06.01 DATASET 1 WORD 1 bits 05 and 06. See chapter Fieldbus
control.
12
12.02 CONST SPD 1 Defines ramped speed 1.
+/- 11.05 EXT1 REF MAX Setting range. 1 = 1 rpm
12.03 CONST SPD 2 Defines ramped speed 2.
+/- 11.05 EXT1 REF MAX Setting range. 1 = 1 rpm
12.04 INCH SPD SEL Selects the activation signal source for the stepped constant speed.
NOT SEL This function is not selected. 1
DI2 Digital input DI2 = 1 selects 12.05 INCH SPD 1. 2
DI3 See selection DI2. 3
DI4 See selection DI2. 4
DI5 See selection DI2. 5
DI6 See selection DI2. 6
DI7 See selection DI2. 7
DI8 See selection DI2. 8
DI9 See selection DI2. 9
DI10 See selection DI2. 10
DI11 See selection DI2. 11
DI12 See selection DI2. 12
FIELDBUS See selection DI2. Instead of a digital input, the selection comes from
06.01 DATASET 1 WORD 1 bit 08. See chapter Fieldbus control.
13
12.05 INCH SPD 1 Defines stepped speed 1.
+/- 11.05 EXT1 REF MAX Setting range. 1 = 1 rpm
12.06 TAKE-UP / PAYOUT Selects the activation signal source for the stepped constant speed
that is added to external speed reference.
Note: This constant speed does not override the speed reference; it is
added to the speed reference.
NOT SEL This function is not selected. 1
DI2 Digital input DI2 = 1 selects 12.07 SPEED CHANGE. 2
DI3 See selection DI2. 3
DI4 See selection DI2. 4
No. Name/Value Description FbEq