Actual signals and parameters
106
62.13 MAX TAPER/% TAPER This parameter is only used if the drive is used to control the dancer
loading. If the drive is not controlling the dancer loading (03.04
DANCER LOAD REF is not sent to an AO) then this parameter can be
ignored.
If MAX TAPER/%TAPER is not 0%, 03.04 DANCER LOAD REF
decreases as 03.13 ROLL DIAMETER increases. At 65.01 MIN CORE
DIAMETER, the taper setpoint is 100%. At 65.02 MAX ROLL
DIAMETER, the taper setpoint is the 62.13 MAX TAPER/%TAPER *
the value from 62.12 TAPER REF SELECT.
0…100% Setting range. 1 = 1%
62.14 MAX DANCER TRAVEL Set to the total mechanical travel of the dancer; the dancer
automatically regulates to the midpoint of this distance. Should it be
desired to have the dancer regulate to something other than midpoint,
enter this offset value into 62.15 CENTER OFFSET.
1.0 …2500.0 mm
1.0 …2500.0 inch
Setting range. 10 = 1 mm
10 = 1 inch
62.15 CENTER OFFSET Desired offset distance from dancer null value (to which dancer
regulates).
-1250.0…1250.0 mm
-1250.0…1250.0 inch
Setting range. 10 = 1 mm
10 = 1 inch
62.23 WEB 2 SELECT Sets or selects the activation signal source for switching the gain and
integration time for the dancer PI regulator.
NOT SEL Not selected. P-GAIN 1 and INTEG TIME 1 are used (62.0162.03). 1
DI2 Digital input DI2 = 1 selects P-GAIN 2 and INTEG TIME 2
(62.2462.26).
2
DI3 See selection DI2. 3
DI4 See selection DI2. 4
DI5 See selection DI2. 5
DI6 See selection DI2. 6
DI7 See selection DI2. 7
DI8 See selection DI2. 8
DI9 See selection DI2. 9
DI10 See selection DI2. 10
DI11 See selection DI2. 11
DI12 See selection DI2. 12
FIELDBUS See selection DI2. Instead of a digital input, the command comes from
06.03 DATASET 1 WORD 3 bit 01. See chapter Fieldbus control.
13
62.24 P-GAIN 2 MIN Optional minimum proportional gain of the dancer PI regulator.
0.01…1000.00 K Setting range. 100 = 1 K
62.25 P-GAIN 2 MAX Optional maximum proportional gain of the dancer PI regulator.
P-GAIN 2 MIN…1000.00 K Setting range. 100 = 1 K
62.26 INTEG TIME 2 Optional integration time of the dancer PI regulator.
10…10000 ms Setting range. 1 = 1 ms
No. Name/Value Description FbEq