Actual signals and parameters
110
63.09 TENSION CTL ENABL Set to “ENABLE” if this is a single position machine and there are no
requirements to ever RUN without tension control.
Set to a DI or FBA option if this is a turret or if there are some
instances where the tension regulation should be ignored in RUN
mode.
NOT SEL Not enabled. The drive is in “pure” speed mode. 1
YES Enabled. When the drive is in run, the tension regulation trim is active. 2
DI2 Digital input DI2 = 1 enables the regulation trim. Otherwise it is in
“pure” speed mode.
3
DI3 See selection DI2. 4
DI4 See selection DI2. 5
DI5 See selection DI2. 6
DI6 See selection DI2. 7
DI7 See selection DI2. 8
DI8 See selection DI2. 9
DI9 See selection DI2. 10
DI10 See selection DI2. 11
DI11 See selection DI2. 12
DI12 See selection DI2. 13
FIELDBUS See selection DI2. Instead of a digital input, the command comes from
06.03 DATASET 1 WORD 3 bit 00. See chapter Fieldbus control.
14
PARAM 63.32 Source selected by 63.32 TEN CTRL ENBL PTR. 15
63.10 TENSION SETPOINT Selects the signal source for setting the tension setpoint.
AI1 Analog input AI1 (voltage). 1
AI2 Analog input AI2 (current). 2
AI3 Analog input AI3 (current). 3
AI5 Analog input AI5 (voltage or current). 4
AI6 Analog input AI6 (voltage or current). 5
FIELDBUS 06.04 DATASET 3 WORD 1. See chapter Fieldbus control. 6
PARAM 63.33 Source selected by 63.33 TEN SETPT PTR. 7
No. Name/Value Description FbEq