Actual signals and parameters
77
FIELDBUS See selection DI2. Instead of a digital input, the selection comes from 
06.01 DATASET 1 WORD 1 bit 07 See chapter Fieldbus control.
13
MASTER DRV The reset signal comes from the master drive. The master drive must 
be stopped (not in RUN).
14
16.05 USER MACRO IO CHG Enables the change of the User Macro through a digital input. See 
99.02 APPLICATION MACRO. The change is only allowed when the 
drive is stopped. During the change, the drive will not start.
Note: Always save the User Macro by 99.02 APPLICATION MACRO, 
after changing any parameter settings, or reperforming the motor 
identification.The
 last settings saved by the user are loaded into use 
whenever the power is switched off and on again or the macro is 
changed. Any unsaved changes will be lost.
Note: The value of this parameter is not included in the User Macro. A 
setting once made remains despite the User Macro change.
NOT SEL User macro change is not possible through a digital input. 1
DI1 Falling edge of digital input DI1: User Macro 1 is loaded into use. 
Rising edge of digital input DI1: User Macro 2 is loaded into use.
2
DI2 See selection DI1. 3
DI3 See selection DI1. 4
DI4 See selection DI1. 5
DI5 See selection DI1. 6
DI6 See selection DI1. 7
DI7 See selection DI1. 8
DI8 See selection DI1. 9
DI9 See selection DI1. 10
DI10 See selection DI1. 11
DI11 See selection DI1. 12
DI12 See selection DI1. 13
FIELDBUS See selection DI1. Instead of a digital input, the selection comes from 
06.01 DATASET 1 WORD 1 bit 01. See chapter Fieldbus control.
14
16.06 LOCAL LOCK Disables entering to local control mode (LOC/REM key of the panel).
WARNING! Before activating, ensure that the control panel is 
not needed for stopping the drive!
OFF Local control allowed. 0
ON Local control disabled. 65535
16.07 PARAMETER SAVE Saves the valid parameter values to the permanent memory. 
Note: A new parameter value of a standard macro is saved 
automatically when changed from the panel but not when altered 
through a fieldbus connection.
DONE Saving started. 0
SAVE… Saving is done. 1
16.09 CTRL BOARD SUPPLY Defines the source of the control board power supply.
Note: If an external supply is used but this parameter has value 
INTERNAL 24 V, the drive trips to a fault at power switch off.
INTERNAL 24 V Internal 1
EXTERNAL 24 V External. The control board is powered from an external supply. 2
No. Name/Value Description FbEq