Technical data 133
The free space requirements are given below.
Losses, cooling data and noise
The inverter is cooled by an internal fan, flow direction from front to top.
1)
for dimensioning the ventilation of the electric equipment room
2)
cooling air flow for a cabinet with one DC input cubicle only
3)
at partial power typically < 65 dB with speed-controlled fans
Terminal and lead-through data for the DC input power
cable
The DC busbars are tin-plated. Cable lugs suited to tin-plated materials can be used.
Required free space around the unit for cooling
Front Side Above Back
mm in. mm in. mm in. mm in.
150 5.91 - - 500 19.68 - -
Required free space for door opening: see chapter Dimension drawings.
Inverter type Heat dissipation
1)
Cooling air flow Noise
Inverter module cubicles Total air flow
2)
kW m
3
/h ft
3
/h m
3
/h ft
3
/h dB
PVS800-57-0100kW-A 4-- 1300 46000 75
PVS800-57-0250kW-A 10 2500 88300 3250 115000
75
3)
PVS800-57-0315kW-B 10 2500 88300 3250 115000
75
3)
PVS800-57-0500kW-A 20 5000 177000 6000 212000
75
3)
PVS800-57-0630kW-B 20 5000 177000 6000 212000
75
3)
PVS800-57-0875kW-B 30 7950 281000 9450 333700 75
PVS800-57-1000kW-C 30 7950 281000 9450 333700 75
Inverter type No. of cable lead-throughs Ø60 mm (2.36”)
+H377 +H382 +2/4/5H382 +8/10H382 +12/15H382 +16/20H382
PVS800-57-0100kW-A 3 × 3 1 × 3 - - - -
PVS800-57-0250kW-A - - 4 × 4 8 × 4 - -
PVS800-57-0315kW-B - - 4 × 4 8 × 4 - -
PVS800-57-0500kW-A - - 4 × 4 8 × 4 12 × 4 -
PVS800-57-0630kW-B - - 4 × 4 8 × 4 12 × 4 -
PVS800-57-0875kW-B - - - 8 × 4 12 × 4 16 x 4
PVS800-57-1000kW-C - - - 8 × 4 12 × 4 16 x 4
IP54
> 500 mm
(19.68 in.)
> 400 mm
(15.75 in.)