Technical data 137
Power factor (cos phi
1
)
adjustment range
0…1 capacitive or inductive depending on the dimensioning
The following graphs illustrate the equipment operation with the nominal AC
voltage and nominal ambient temperature. See Ratings on page 123.
Current See section Ratings.
Overvoltage category
(IEC 62109, IEC 60664-1)
3 (With option +F263, the category is 1.)
Harmonic distortion THD current < 3% at nominal load
DC input connection data
Maximum DC power (P
pv
) See section Ratings.
Maximum DC current
(I
max(DC)
)
See section Ratings.
Maximum DC voltage
(U
max(DC)
)
Types -0100kW-A, -0250kW-A and -0315kW-B: 1000 V DC
Types -0500kW-A, -0630kW-B, -0875kW-B and -1000kW-C: 1100 V DC
Operational DC voltage
range, U
mppt(DC)
Types -0100kW-A, -0250kW-A and -0500kW-A: 450…825 V DC
Types -0315kW-B, -0630kW-B and -0875kW-B: 525…825 V DC
Type -1000kW-C: 600…850 V DC
Voltage ripple < 3%
Overvoltage category
(IEC 62109, IEC 60664-1)
2
P/P
N
(%)
90
80
70
60
50
40
30
20
10
0
-10
-20
-30
-40
-50
-60
-70
-80
10 20 30 40 50 60 70 80 90 1000
100
-90
-100
Q (%)
P/P
N
(%)
Q (%)
90
80
70
60
50
40
30
20
10
0
-10
-20
-30
-40
-50
-60
-70
-80
10 20 30 40 50 60 70 80 90 1000
100
-90
-100
Q Reactive power in percentage of nominal active power
P/P
N
Relative active power
Types -0100kW-A and -0250kW-A Types -0315kW-B, -0500kW-A, 0630kW-B, -0875kW-B,
-1000kW-C
10 000 - P
act
2
Q
max =
Q
max
= 0.9 ·
10 000 - P
act
2