Electrical installation 87
AC output cable connection procedure
1. Remove the shroud covering the output power terminals.
2. Lead the cable(s) into the inside of the cabinet. If a shielded cable is used, prepare the
cable ends and make the 360° grounding arrangements at the cabinet entry as shown
on the next page. Connect the twisted shield of the AC output cable(s) to the cabinet
PE (ground) busbar with a cable lug.
3. Connect the phase conductors to terminals L1, L2 and L3. Connect the separate
PE/grounding conductor (if present) to the cabinet PE (ground) busbar.
4. Refit the shroud onto the output power terminals.
AC output terminals of PVS800-57-1000kW
a) 360 degrees EMC lead-throughs
b) Cable support
L2
L3
L1
PE
a
b
PE