146 Technical data
Auxiliary circuit power consumption
The auxiliary circuit must be supplied by the customer galvanically separated
from inverter output.
Inverter type Total in running max.
(W)
Total in stand-by (W) Additional
consumption in stand-
by (option +G300)
(max. W)
PVS800-57-0100kW-A 310 60 150
PVS800-57-0250kW-A 310 60 250
PVS800-57-0315kW-B 310 60 250
PVS800-57-0500kW-A 490 65 350
PVS800-57-0630kW-B 490 65 350
PVS800-57-0875kW-B 650 65 450
PVS800-57-1000kW-C 650 65 450
Notes:
The values above do not include the cooling fans of the inverter modules.
Their power is taken from the solar generator.
Every additional incoming cubicle increases the auxiliary power
consumption by 50 W in PVS800-57-0100kW-A…PVS800-57-0630kW-B
and by 25 W in PVS800-57-0875kW-B…PVS800-57-1000kW-C.
The actual consumption depends on the options installed.
Option +G300
: The actual power consumption depends on temperature.
Option +G410:
Maximum power consumption 20 W per junction box.
The auxiliary circuit has to be protected with 16 A gG fuses. See the circuit
diagrams delivered with the inverter.