148 Technical data
Medium voltage network
The requirements of the EMC Directive can be met as follows:
1. A transformer with static screening between the primary and secondary windings is used to ensure that
no excessive emission is propagated to neighboring low-voltage networks.
2. The inverter is installed to an IT (ungrounded) system according to the instructions given in the hardware
manual.
Low-voltage network
The requirements of the EMC Directive can be met as follows:
1. A transformer with static screening between the primary and secondary windings is used to ensure that
no excessive emission is propagated to neighboring low-voltage networks.
2. The low-voltage network is of the TN type (grounded).
3. The EMC filter (option +E216) is installed on network side of the low-voltage transformer.
4. The inverter is installed according to the instructions given in the hardware manual.
“C-tick” marking
“C-tick” marking is required in Australia and New Zealand. A “C-tick” mark is attached to the inverter to verify
compliance with the relevant standards IEC/EN 61000-6-2:2005 and IEC/EN 61000-6-4:2007, mandated by
the Trans-Tasman Electromagnetic Compatibility Scheme.
For fulfilling the requirements of the standard, see section Compliance with the European EMC directive on
page 147.
PVS800
Low-voltage
network
Equipment
Equipment
Medium voltage network
Static screen
Neighboring network
PVS800
Equipment
Low-voltage network
Static screen
EMC filter
1)
1)
option +E216