Settings
Table 75: DEFPTOC Settings
Name
Values (Range) Unit Step Default Description
Operation Off
On
- - On Operation Off/On
Start Value 4…200
200…1000
A
A
1
5
4 Start value for earth-
fault detection
Voltage Start Value 500..1000 V 1 500 Voltage start value
Operate Delay Time 40…60000 ms 10 80 Operate delay time
Enable Voltage Limit No
Yes
- - Yes Additional check for
voltage before
issuing trip
Directional Mode
Forward
Reverse
Non Directional
-
- Forward Directional mode
Operation Mode Phase angle
IoSin
IoCos
-
- Phase angle Operation criteria
Characteristics
Angle
-179…180 Deg 1 0 Characteristics
angle
Max Forward Angle 0…180 Deg 1 80 Maximum phase
angle in forward
direction
Max Reverse Angle
0…180 Deg 1 80 Maximum phase
angle in reverse
direction
Min Forward Angle
0…180 Deg 1 80 Minimum phase
angle in forward
direction
Min Reverse Angle
0…180 Deg 1 80 Minimum phase
angle in reverse
direction
Min Operate Current
- A - 1 Minimum operating
current to allow
directional criteria
Min Operate Voltage
- V - 500 Minimum operating
voltage to allow
directional criteria
Abs Hyst Oper Qty
0.0…50.0 A 0.1 0.1 Absolute hysteresis
for operating
quantity
Abs Hyst Pol Qty
0…2500 V 0.1 200 Absolute hysteresis
for polarizing
quantity
Section 6 1MRS757488 H
Commissioning
116 RIO600
Installation and Commissioning Manual