7.2.13 LD0.VMHAI voltage total demand distortion
Table 138: LD0.VMHAI voltage total demand distortion
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.VMHAI1 SIM8F-1
533 385.05 .HiAThd.stVal Voltage THD 1 = Operate
LD0.VMHAI2 SIM8F-2
565 387.05 .HiAThd.stVal Voltage THD 1 = Operate
LD0.VMHAI3 SIM8F-3
661 801.05 .HiAThd.stVal Voltage THD 1 = Operate
LD0.VMHAI4 SIM8F-4
693 803.05 .HiAThd.stVal Voltage THD 1 = Operate
LD0.VMHAI5 SIM8F-5
725 805.05 .HiAThd.stVal Voltage THD 1 = Operate
7.2.14 LD0.EFPTOC non-directional earth-fault detection
Table 139: LD0.EFPTOC non-directional earth-fault detection
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.EFPTOC1 SIM8F-1/SIM4F-1
534 385.06 .Str.general START General Start 1 = Start
535 385.07 .Op.general Operate General Operate 1 = Operate
LD0.EFPTOC2 SIM8F-2/SIM4F-2
566 387.06 .Str.general START General Start 1 = Start
567 387.07 .Op.general Operate General Operate 1 = Operate
LD0.EFPTOC3 SIM8F-3/SIM4F-3
662 801.06 .Str.general START General Start 1 = Start
663 801.07 .Op.general Operate General Operate 1 = Operate
LD0.EFPTOC4 SIM8F-4/SIM4F-4
694 803.06 .Str.general START General Start 1 = Start
695 803.07 .Op.general Operate General Operate 1 = Operate
LD0.EFPTOC5 SIM8F-5/SIM4F-5
726 805.06 .Str.general START General Start 1 = Start
727 805.07 .Op.general Operate General Operate 1 = Operate
1MRS757488 H Section 7
Modbus TCP communication
RIO600 211
Installation and Commissioning Manual