5.2 Connecting wires
5.2.1 Connecting power supply
RIO600 supports power supply modules PSMH and PSML.
With the PSMH module, the voltage range for the external power connection is
110...250 V DC (±20%) and 100...240 V AC (-15% to +10%).
With the PSML module, the voltage range for the external power connection is U
aux
nominal 24, 30, 48, 60 V DC (with variation of 50...120% of Un) and the startup
threshold is 19.2 V DC (24 V DC * 80%).
1. Fasten the power connector through the upper and lower screw terminals.
2. Connect the power supply cable to the power supply module.
1MRS757488 H Section 5
Installing
RIO600 33
Installation and Commissioning Manual