EasyManua.ls Logo

ABB Remote I/O RIO600 - Section 10 Technical data

ABB Remote I/O RIO600
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 10 Technical data
Table 187: Interfaces
Description Value
LECM Ethernet interface RJ-45 (STP CAT5e) galvanic connector
Multimode LC fiber-optic connector
Power Supply Module (PSMH/PSML/DIM8H/
DIM8L/DOM4/SCM8H/SCM8L) front mating
connector
Suggested part: Weidmuller P/N 1844260000
Sensor input module SIM8F/SIM4F
Table 188: Module weights
Description Value
PSMH/PSML 235 g
LECM 123 g
DIM8H/DIM8L 206 g
DOM4 163 g
RTD4 206 g
AOM4 206 g
SIM8F/SIM4F 180 g
SCM8H/SCM8L 215 g
Table 189: Dimensions of the end clamp (EW 35, Weidmuller)
Description
Value
Width 8.5 mm (to be fixed at the ends of assembled
modules)
Table 190: Power supply
Description
PSMH PSML
U
aux
nominal 100, 110, 120, 220, 240 V AC,
50 and 60 Hz
24, 30, 48, 60 V DC
110, 125, 220, 250 V DC
U
aux
variation 85…110% of U
aux
nominal
(85...264 V AC)
50...120% of U
aux
nominal
(12...72 V DC)
80…120% of U
aux
nominal
(88…300 V DC)
Start-up threshold 19.2 V DC (24 V DC × 80%)
Table continues on next page
1MRS757488 H Section 10
Technical data
RIO600 285
Installation and Commissioning Manual