Table 184: Behavior during IRF in SIM8F module
Module IRF Behavior in an IRF condition
RIO600 as a whole LECM DIM8L/DIM8H, DOM4, RTD4,
AOM4
IRF in SIM8F module Continues normal function with
corrective action
1. Shows IRF by steady IRF
LED on LECM module
2. Shows IRF source
information on WHMI
under faults page
3. SIM8F module information
is sent with bad quality
4. GOOSE: Updates quality
of all modules' data
attributes and RIO600
module health as per IEC
61850
5. Opens DOM4 IRF output
contact, if it is configured
1. Continues normal
operation
2. Shows error in previous
module over LECM WHMI
(if detected)
Table 185: Behavior during IRF in SIM4F module
Module IRF Behavior in an IRF condition
RIO600 as a whole LECM DIM8L/DIM8H, DOM4,
RTD4, AOM4
IRF in SIM4F module Continues normal
function with corrective
action
1. Shows IRF by
steady IRF LED
on LECM module
2. Shows IRF
source
information on
WHMI under
faults page
3. SIM4F module
information is
sent with bad
quality
4. GOOSE:
Updates quality
of all modules'
data attributes
and RIO600
module health as
per IEC 61850
5. Opens DOM4
IRF output
contact, if it is
configured
1. Continues normal
operation
2. Shows error in
previous module
over LECM
WHMI (if
detected)
9.2 Restoring communication
1. Check the firewall configuration in the host PC. A firewall may prevent the FTP
and ping command from working.
2. Open the TCP/IP and UDP ports by adjusting the firewall settings.
Section 9 1MRS757488 H
Troubleshooting
280 RIO600
Installation and Commissioning Manual