Reg A Scale IEC 61850 name SA name Description Values
208 Value reported to user with a
scale factor of "1" when
channel configured as
dimensionless and with a scale
factor of "100" when channel
configured as either mA or
RTD
.AnIn1.mag.f
RTD 10-Channel 1 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
209 .AnIn2.mag.f RTD 10-Channel 2 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
210 .AnIn3.mag.f RTD 10-Channel 3 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
211 .AnIn4.mag.f RTD 10-Channel 4 Input Value -40...200 [°C]/0.0...20.0
[mA]/-10000...10000
1)
212 <reserved> <reserved> 0
213 <reserved> <reserved> 0
214 <reserved> <reserved> 0
215 <reserved> <reserved> 0
216 .AnIn1.range/.An
In2.range
RTD 10- Channel Range Information
Channel - 2 (High Byte)
Channel - 1 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
217
.AnIn3.range/.An
In4.range
RTD 10- Channel Range Information
Channel - 4 (High Byte)
Channel - 3 (Low Byte)
Normal – 0;
High – 1;
Low – 2;
High High – 3;
Low Low – 4;
218
<reserved> <reserved> 0
219 <reserved> <reserved> 0
220 <reserved> <reserved> 0
221 <reserved> <reserved> 0
222 <reserved> <reserved> 0
223 <reserved> <reserved> 0
1) As per the configuration
7.2.8 LD0.RTDGGIO RTD channel range information
RTD input channel range information can be accessed with addresses listed in the
table.
Section 7 1MRS757488 H
Modbus TCP communication
202 RIO600
Installation and Commissioning Manual