Reg A Type Scale IEC 61850 name SA name Description Values
0.06 Bit Module 5 Health 0 = Ok,
1 = Warning
or error
0.07
Bit Module 6 Health 0 = Ok,
1 = Warning
or error
0.08
Bit Module 7 Health 0 = Ok,
1 = Warning
or error
0.09
Bit Module 8 Health 0 = Ok,
1 = Warning
or error
0.1
Bit Module 9 Health 0 = Ok,
1 = Warning
or error
0.11
Bit Module 10 Health 0 = Ok,
1 = Warning
or error
0.12
Bit UPS Power Failure Status 0 = Ok,
1 = Warning
or error
0.13
Bit Local/Remote Mode Status 0 = Remote,
1 = Local
0.14 Bit <reserved> 0
0.15 Bit <reserved> 0
7.2.2 SSR2 System status register (2) device alive register
This register provides information about the Modbus device alive counter.
Table 127: SSR2 System status register (2) device alive register
Reg A
Type Scale IEC 61850 name SA name Description Values
1 u16 1 Device Alive Counter 0...65535
7.2.3 Time synchronization
RIO600 time can be synchronized with the Modbus client by writing to the register
addresses in Table 20. The time can also be read from the same register addresses.
Table 128: Time synchronization
Reg A
Type Scale IEC 61850 name SA name Description Values
8 u16 1 Year 2000...2999
9 u16 1 Month 1...12
10 u16 1 Day 1...31
11 u16 1 Hour 0...23
12 u16 1 Minute 0...59
13 u16 1 Second 0...59
1MRS757488 H Section 7
Modbus TCP communication
RIO600 185
Installation and Commissioning Manual