Bit A Reg A IEC 61850 name SA name Description Values
853 813.05 .Str.general START General Start 1 = Start
LD0.SEQSPVC5 SIM8F-5
885 815.05 .Str.general START General Start 1 = Start
7.2.21 LD0.INRPHAR inrush detector
Table 146: LD0.INRPHAR inrush detector
Bit A Reg A IEC 61850 name SA name Description Values
LD0.INRPHAR1 SIM8F-1/SIM4F-1
758 807.06 .Str.general START General Start 1 = Start
LD0.INRPHAR2 SIM8F-2/SIM4F-2
790 809.06 .Str.general START General Start 1 = Start
LD0.INRPHAR3 SIM8F-3/SIM4F-3
822 811.06 .Str.general START General Start 1 = Start
LD0.INRPHAR4 SIM8F-4/SIM4F-4
854 813.06 .Str.general START General Start 1 = Start
LD0.INRPHAR5 SIM8F-5/SIM4F-5
886 815.06 .Str.general START General Start 1 = Start
7.2.22 Binary writable signals for SIM8F
Table 147: Binary writable signals for SIM8F
Bit A
Reg A IEC 61850 name SA name Description Values
SIM8F-1
576 391 Reset Fault Indicator 1 = Reset
577 391.01 Reset Energy Counter 1 = Reset
578 391.02 Update Statistics
1 = Update
statistics
SIM8F-2
592 392 Reset Fault Indicator 1 = Reset
593 392.01 Reset Energy Counter 1 = Reset
594 392.02 Update Statistics
1 = Update
statistics
SIM8F-3
896 816 Reset Fault Indicator 1 = Reset
897 816.01 Reset Energy Counter 1 = Reset
898 816.02 Update Statistics
1 = Update
statistics
SIM8F-4
912 817 Reset Fault Indicator 1 = Reset
Table continues on next page
Section 7 1MRS757488 H
Modbus TCP communication
216 RIO600
Installation and Commissioning Manual