Reg A Type Scale IEC 61850 name SA name Description Values
1092 i32 10 .A.phB.cVal.mag.f Phase B Peak Current
1093
1094 i32 10 .A.phC.cVal.mag.f Phase C Peak Current
1095
LD0.CMAMMXU5 SIM8F-5/SIM4F-5
1222 i32 10 .A.phA.cVal.mag.f Phase A Peak Current
1223
1224 i32 10 .A.phB.cVal.mag.f Phase B Peak Current
1225
1226 i32 10 .A.phC.cVal.mag.f Phase C Peak Current
1227
7.2.37 LD0.VAVMMXU average voltage measurements
Table 162: LD0.VAVMMXU average voltage measurements
Reg A Type Scale IEC 61850 name SA name Description Values
LD0.VAVMMXU1 SIM8F-1
500 i32 1 .PhsV.phsA.cVal.mag.f Phase A Average Operating
Voltage
501
502 i32 1 .PhsV.phsB.cVal.mag.f Phase B Average Operating
Voltage
503
504 i32 1 .PhsV.phsC.cVal.mag.f Phase C Average Operating
Voltage
505
LD0.VAVMMXU2 SIM8F-2
632 i32 1 .PhsV.phsA.cVal.mag.f Phase A Average Operating
Voltage
633
634 i32 1 .PhsV.phsB.cVal.mag.f Phase B Average Operating
Voltage
635
636 i32 1 .PhsV.phsC.cVal.mag.f Phase C Average Operating
Voltage
637
LD0.VAVMMXU3 SIM8F-3
964 i32 1 .PhsV.phsA.cVal.mag.f Phase A Average Operating
Voltage
965
Table continues on next page
1MRS757488 H Section 7
Modbus TCP communication
RIO600 235