3.5.1 TCP/IP-based protocols and used IP ports
The RIO600 device supports FTP, HTTP, Modbus TCP and the network time
management protocols.
Table 4: Supported ports in the RIO600 device
Port number Type Default state Description
20, 21 TCP Open File transfer protocol
(FTP)
123 UDP Open Network time
management protocol
80 TCP Open Web server HTTP
502 TCP Closed Modbus TCP
FTP and HTTP protocols are not secure. Ensure general security in the
substation is considered as described in General security deployment
guidelines.
FTP and HTTP are always enabled and cannot be disabled.
For the FTP protocol, it is strongly recommended to change the
default password using IED Users Management in PCM600 as
described in the communication configuration manual. The default
password in RIO600 for the ADMINISTRATOR user credential is
“ABB_RIO600”==/”.
RIO600 supports only one user credential for ADMINISTRATOR.
Modbus is disabled by default and can be enabled with Parameter
Settings in PCM600. In the plant structure, go to RIO600/IED
Configuration/Configuration/Station Communication/
MODBUS: 0 to set the Modbus configuration parameters.
Section 3 1MRS757488 H
RIO600 overview
22 RIO600
Installation and Commissioning Manual