GUID-0D76E7F2-D359-42D6-B774-D1E8D37EF4D6 V1 EN
Figure 82: Configuring the UPS power failure input channel
6.1.6.11 Calibration
The SIM8F module is factory calibrated.
6.1.7 Operating parameter settings of SIM4F module
Table 97: Operating parameter settings of SIM4F module
Parameter name
Range Unit Step Default Description
Frequency 50
60
Hz - 50 Hz Rated system
frequency
Nominal current 80…630 A 1 400 Nominal phase
current
Rated sensor current 80
250
A - 80 Rated primary
current of sensor
Io signal sel Calculated Io
Measured Io
- - Calculated Io Selection used
for Io signal
Phase Rotation ABC
ACB
- - ABC Phase rotation
order
Sensor Correction Factors
Table continues on next page
1MRS757488 H Section 6
Commissioning
RIO600 147
Installation and Commissioning Manual