Parameter name Range Unit Step Default Description
Phase A Current
Amplitude
0.7000…1.3000 - 0.0001 1 Amplitude
correction factor
for current
sensor, phase A
Current Phase
-3.0000…
+3.0000
deg 0.0003 0 Phase correction
factor for current
sensor, phase A
Phase B
Current
Amplitude
0.7000…1.3000 - 0.0001 1 Amplitude
correction factor
for current
sensor, phase B
Current Phase
-3.0000…
+3.0000
deg 0.0003 0 Phase correction
factor for current
sensor, phase B
Phase C
Current
Amplitude
0.7000…1.3000 - 0.0001 1 Amplitude
correction factor
for current
sensor, phase C
Current Phase
-3.0000…
+3.0000
deg 0.0003 0 Phase correction
factor for current
sensor, phase C
Residual
Current
Amplitude
0.7000…1.3000 - 0.0001 1 Amplitude
correction factor
for current
sensor, residual
Current Phase
-3.0000…
+3.0000
deg 0.0003 0 Phase correction
factor for current
sensor, residual
LED reset time delay
1…1440 min 1 60 LEDs Reset
delay time
(incase no
external signal
received for
resetting). This is
applicable to OC
fault detection &
EF Protection
LEDs.
Fault Indication Reset Method Self Reset
Method
Definite Time
-
- Definite Time Self Reset
Method: Flashing
protection
indication LED is
reset
immediately
once the fault is
cleared.
Definite Time:
Flashing
protection
indication LED is
reset after the
definite time set
by LED reset
time delay.
Update interval for Metering values 1...15 - 1 4 Update interval
for metering
values
x500mSec
Section 6 1MRS757488 H
Commissioning
148 RIO600
Installation and Commissioning Manual