Bit A Reg A IEC 61850 name SA name Description Values
685 802.13 .Str.phsA Phase A Start 1 = Start
686 802.14 .Str.phsB Phase B Start 1 = Start
687 802.15 .Str.phsC Phase C Start 1 = Start
688 803.00 .Op.general Operate General Operate 1 = Operate
689 803.01 .Op.phsA Phase A Operate 1 = Operate
690 803.02 .Op.phsB Phase B Operate 1 = Operate
691 803.03 .Op.phsC Phase C Operate 1 = Operate
698 803.10 .OpFwd.general Forward Operate 1 = Operate
699 803.11 .OpRev.general Reverse Operate 1 = Operate
LD0.DPHPTOC5 SIM8F-5
716 804.12 .Str.general START General Start 1 = Start
717 804.13 .Str.phsA Phase A Start 1 = Start
718 804.14 .Str.phsB Phase B Start 1 = Start
719 804.15 .Str.phsC Phase C Start 1 = Start
720 805.00 .Op.general Operate General Operate 1 = Operate
721 805.01 .Op.phsA Phase A Operate 1 = Operate
722 805.02 .Op.phsB Phase B Operate 1 = Operate
723 805.03 .Op.phsC Phase C Operate 1 = Operate
730 805.10 .OpFwd.general Forward Operate 1 = Operate
731 805.11 .OpRev.general Reverse Operate 1 = Operate
7.2.12 LD0.CMHAI current total demand distortion
Table 137: LD0.CMHAI current total demand distortion
Bit A
Reg A IEC 61850 name SA name Description Values
LD0.CMHAI1 SIM8F-1
532 385.04 .HiATdd.stVal
Current TDD Upto 8th
Harmonics 1 = Operate
LD0.CMHAI2 SIM8F-2
564 387.04 .HiATdd.stVal
Current TDD Upto 8th
Harmonics 1 = Operate
LD0.CMHAI3 SIM8F-3
660 801.04 .HiATdd.stVal
Current TDD Upto 8th
Harmonics 1 = Operate
LD0.CMHAI4 SIM8F-4
692 803.04 .HiATdd.stVal
Current TDD Upto 8th
Harmonics 1 = Operate
LD0.CMHAI5 SIM8F-5
724 805.04 .HiATdd.stVal
Current TDD Upto 8th
Harmonics 1 = Operate
Section 7 1MRS757488 H